Model |
Nominal Voltage (V) |
Rated Capacity (Ah) 10Hr. To 1.75V/Cell |
Dimensions (in) mm |
Weight (Lb) kg |
Length |
Width |
Height |
Overall Height |
without electrolyte |
with electrolyte |
"OPzS" STATIONARY BATTERIES - TELECOM/UPS (15 Year Design) |
4 OPzS (A) 200 |
2 |
200 |
(4.09) 104 |
(8.15) 207 |
(14.02) 356 |
(16.06) 408 |
(27.34) 12.4 |
(35.71) 16.2 |
5 OPzS (A) 250 |
2 |
250 |
(4.92) 125 |
(8.15) 207 |
(14.02) 356 |
(16.06) 408 |
(32.63) 14.8 |
(43.21) 19.6 |
6 OPzS (A) 300 |
2 |
300 |
(5.75) 146 |
(8.15) 207 |
(14.02) 356 |
(16.06) 408 |
(37.70) 17.1 |
(50.49) 22.9 |
5 OPzS (A) 350 |
2 |
350 |
(4.92) 125 |
(8.15) 207 |
(18.58) 472 |
(20.63) 524 |
(45.19) 20.5 |
(62.61) 28.4 |
6 OPzS (A) 420 |
2 |
420 |
(5.75) 146 |
(8.15) 207 |
(18.58) 472 |
(20.63) 524 |
(52.47) 23.8 |
(73.19) 33.2 |
7 OPzS (A) 490 |
2 |
490 |
(6.57) 167 |
(8.15) 207 |
(18.58) 472 |
(20.63) 524 |
(59.74) 27.1 |
(83.55) 37.9 |
6 OPzS (A) 600 |
2 |
600 |
(5.75) 146 |
(8.15) 207 |
(25.47) 647 |
(27.52) 699 |
(71.65) 32.5 |
(97.66) 44.3 |
8 OPzS (A) 800 |
2 |
800 |
(7.56) 192 |
(8.31) 211 |
(25.47) 647 |
(27.52) 699 |
(97.88) 44.4 |
(134.26) 60.9 |
10 OPzS (A) 1000 |
2 |
1,000 |
(9.21) 234 |
(8.31) 211 |
(25.47) 647 |
(27.52) 699 |
(119.05) 54.0 |
(164.24) 74.5 |
12 OPzS (A) 1200 |
2 |
1,200 |
(10.87) 276 |
(8.31) 211 |
(25.47) 647 |
(27.52) 699 |
(139.33) 63.2 |
(194.00) 88.0 |
12 OPzS (A) 1500 |
2 |
1,500 |
(10.87) 276 |
(8.31) 211 |
(31.42) 798 |
(33.46) 850 |
(179.89) 81.6 |
(250.44) 113.6 |
16 OPzS (A) 2000 |
2 |
2,000 |
(15.75) 400 |
(8.46) 215 |
(30.43) 773 |
(32.48) 825 |
(241.18) 109.4 |
(346.34) 157.1 |
20 OPzS (A) 2500 |
2 |
2,500 |
(19.21) 488 |
(8.46) 215 |
(30.43) 773 |
(32.48) 825 |
(302.69) 137.3 |
(428.35) 194.3 |
24 OPzS (A) 3000 |
2 |
3,000 |
(22.72) 577 |
(8.46) 215 |
(30.43) 773 |
(32.48) 825 |
(354.72) 160.9 |
(506.17) 229.6 |
|
Advantages
* Compliant to DIN 40736 and DIN 40737.
* The optimized plate design results in increased capacities over DIN standards.
* Minimum maintenance due to reduced antimony content and large electrolyte reserve volume.
* Ideal for cycling applications due to the tubular plate technique.
* Long design life time: more than 15 years in floating applications.
* Available in 2V Cells, 6V and 12V monoblocks.
* Delivery in dry charged or wet charged conditions.
* Long storage time for cells delivered in dry charged condition.
* Suitable for all standard types of installation.
|
 |
 |
| |